We have installed a Gree LSQWF130VM on a glycol loop. It's a 130 kW air-cooled modular scroll chiller with dual systems and two AP1 main boards. It was commissioned a couple of weeks ago in New Zealand. I'd like to read its status into Home Assistant: leaving/entering glycol temp, run state, fault codes, compressor status. Read-only. I'm not trying to control it.
What I've found so far:
No LSQWF point table or BMS terminal spec online. The closest manual is the LSQWRF130VM/NhA-M installation manual, and it doesn't cover Modbus.
The A-Series manuals say the BMS link is RS485 through the FG30-00/A(M) remote-monitoring kit. As far as I can tell, that kit is PC monitoring software, not a Modbus gateway.
One manual puts the display panel on CN4, with a spare CN47 on the main board. It also says Gree supplies a Modbus protocol "on request".
I'm guessing the Gree gateways for other ranges (ME30-24/E6, D1(BM)) won't work with this unit.
Questions:
Has anyone got Modbus RTU data off one of these, or another Gree modular chiller of the same generation? Which port did you use: CN47, a BMS terminal, or a gateway?
Does anyone have the Modbus register map, or know the part number of the right gateway?
Comms settings: I'm guessing 9600 8N1, function 03, temperatures ×0.1. Can anyone confirm or correct that?
Did you get the protocol doc from the Gree distributor? How long did it take?
I'd rather poll a proper BMS port than tap the controller–display bus, so I'm after the sanctioned route. I'm happy to share the map back here if I get one. Thanks.