Got a 2012 modulating 97AFUE nat gas furnace (Comfortmaker, ICP/Carrier product). It has been a great and efficient furnace for 14 years, so no complaints.
Recently checked it to get ready for this winter season, but it won’t fire. I diagnosed it as a stuck gas valve and already ordered the part. It’s big money (close to $400), so give me a sanity check on my diagnosis if you will.
- Calling for heat, furnace starts inducer motor, closes pressure switches ok, lights hot surface igniter (which glows a bright orange as always), gas valve clicks, but no flame is established. Gas valve remains actuated for about three seconds, and then the board closes it.
-Furnace blinked error code 4 (high limit trip), tries to reignite four more times and then locks down with error code 7 (high limit lockout).
-I checked the high temp limit and the two flame rollout sensors which are all normally closed and received 27V from the transformer. I checked them during idle and under load (when the gas valve clicks). Circuit held steady at 27V
-I checked whether the gas valve receives 27V when actuated, and it does.
-I checked the circuit board under load at the R and COM terminal, and it holds 27V when the gas valve clicks.
-I then tested incoming gas pressure (about 8 in WC) and outgoing gas pressure during valve actuation. There was no detectable pressure at all on the output side. Reading remained literally at 0 in WC. There was an ever so slight whiff of nat. gas after triggering it, so I assume a tiny bit of gas made it through.
-Somewhere in the middle of all this testing, the furnace started throwing code 6 (ignition proving fault) (instead of code 4) which is more consistent with what’s happening (no flame established).
I concluded from this that the board seems ok and that the gas valve must be stuck. It’s been sitting unused for the whole summer, so quite possible. Since repairing this valve isn’t really a safe option, I ordered the replacement model and will put it in next weekend.
Only weird thing in this whole adventure is the code 4 (limit trip) as no flame was ever established to begin with. As I said, I checked the entire limit circuit upstream and downstream from where it exits the board and returns to it.
I wonder if the limit fault code could have been triggered by the gas valve’s internals? It is modulating and receives an input signal for the capacity modulation as well (in addition to the main valve on and off signal).
Lastly, since the valve’s outlet produced no pressure upon actuation, I figured it must be the valve.
Your input is welcome. Thanks for reading this!