Is this hot tub electrical installation as concerning as I think it is?
I recently hired an electrician to install a new outdoor subpanel and two circuits at my lake house in Missouri:
- 50A/240V GFCI circuit for an Arctic Spas hot tub.
- 20A/120V circuit for an outdoor pavilion.
I have only a basic understanding of electrical systems, but during my final inspection, I noticed several things that prompted me to research the NEC requirements. I identified the following four concerns:
- Hot tub wiring
Encore 6/3 NM-B cable was installed through underground PVC conduit beneath a newly poured concrete patio. My understanding is that NM-B is not rated for wet locations, regardless of whether it is installed inside conduit. I also understand that the outdoor hot tub circuit requires an insulated copper grounding conductor.
- Pavilion wiring
The 20A circuit consists of individual black and white insulated conductors and a bare copper ground running through underground conduit. There are approximately 3–4 feet of exposed wiring, and neither insulated conductor has any identification markings whatsoever. I suspect these conductors may have been removed from NM-B cable rather than being individually rated THWN-2 conductors.
- Subpanel enclosure
The electrician installed an Eaton 125A load center explicitly labeled “Type 1 Enclosure – Indoor.” It is mounted underneath the house, only 20 inches from the edge of the overhang. The area is open-sided and susceptible to wind-driven rain, snow and outdoor moisture. I would have expected a NEMA 3R outdoor-rated enclosure.
- Subpanel feeder
The incoming feeder from the existing electrical panel is Priority Wire 2-2-2 aluminum Type SE Style U (SEU) cable, containing two insulated conductors and one bare concentric conductor.
Given that the new subpanel supplies both 240V and 120V circuits, my understanding is that a four-conductor feeder with separate neutral and equipment grounding conductors is required. I cannot identify a separate equipment grounding path.
I’ve communicated these concerns to the electrician respectfully, cited the relevant NEC provisions and given him an opportunity to respond and remedy the installation. He has historically been very responsive but has not yet responded to my concerns.
I’m not looking to tell an electrician how to do his job, nor am I looking for an excuse to avoid paying for his work. I simply want a safe, code-compliant installation.
I’d appreciate some objective feedback from experienced electricians:
- Are all four of my concerns justified?
- Are there any legitimate code exceptions or installation considerations I may be overlooking?
- How serious are these deficiencies from a practical safety standpoint?
- What would you recommend to correct them?
- Would you be comfortable with this installation at your own home?
The hot tub is scheduled to be delivered and installed in approximately one week. I’ve attached photographs of the installation, wiring markings, subpanel label and internal connections.