r/firealarms • u/imakebuildingsscream • 9h ago
Discussion Firelite 9600udls nuisance alarms
I got an emergency call for a bunch of nuisance alarms somewhere. Arrived on site checked history the only thing in history was ac fault troubles and clears. Used ps tools and pulled the full history found that the fault came in and cleared about 20 times every minute but did not show anything on the face. Found power supply was having a very quick interment ground fault on the hot and neutral terminals with power shut off. Only thing I could figure out is power supply was bad and that it was causing the panel to kinda freak out and just send random smokes into alarm had 3 pop up while troubleshooting about 2 hours while pulling history and sensitivity test on smokes all well within range. Once I killed ac power fault stopped and panel ran off battery backup for 1 hour no alarms came in. Has anyone else run into this problem? Is this a normal thing for these panels to do if the power supply goes bad?