r/verticalfarming • u/Ashamed_Reference_99 • 9h ago
Lights-off humidity spike: are people sizing dehumidifiers for the night condition, or only for the catalog rating?
One of the more consistent issues I see on indoor cultivation rooms is the lights-off humidity spike.
During the photoperiod the room is warmer, the plants are transpiring, and a refrigerant dehumidifier is usually running closer to the warm, humid conditions it was rated at. When the lights go off, the dry-bulb drops fairly quickly, RH jumps, and the plants are still giving off moisture. The coil is now seeing cooler air, so moisture-removal capacity falls off right as that overnight latent load is still there. If the unit was sized only from a catalog number at a warm rating point, the room can sit wet for hours even though the same machine looked big enough on paper.
Curious how commercial operators and the contractors who build these rooms are actually handling that. Are you sizing to the lights-off temperature and the overnight moisture load, keeping the room from dropping as hard when the lights go off, or controlling to dew point or absolute humidity instead of a daytime RH setpoint?
Not looking for a product suggestion, just what's been reliable in rooms that run year-round.