I have an LG Dual Inverter 12k (12,000 BTU) that isn't performing. I built an app that pulls its data from LG's cloud, and I saw that the compressor goes up to about 700 to 800 W, holds for around 20 minutes, then throttles down to 500 to 600 W when the indoor coil sensor gets close to 9 °C. That's the anti-freeze protection kicking in. The limit seems to be 8, it throttles around 9 and tries to hold the coil there. It used to hit about 1000 W at startup to pull the room down.
In the afternoon it stays stuck at 500 to 600 W and the room doesn't cool properly. The wall it's mounted on gets sun all day and never drops below 30 °C. It hurts at night too. I set 24 and it only gets there around 2 a.m. Only then does it ramp down and save energy, and around 6 a.m. the room starts warming up again because it can't raise its power when it needs to.
Today I pulled the coil sensor off the pipe and it started performing again. It ran at full power for 3 to 4 hours, the wall dropped to 22 or 23 °C and the room got down to 19 or 20 °C. The coil didn't freeze.
In the app every sensor reads values that make sense, condenser, outdoor air, compressor and coil. I measured the coil pipe with a probe on my multimeter and it matches what the board reads, so the sensor is fine. The coil is clean. I also recharged the refrigerant from scratch, weighed in, so it's not the charge.
My question is whether 8 to 9 °C is really LG's threshold for the coil protection, or whether it should go lower. From what I've seen there's still plenty of margin before it freezes. Does anyone know at what temperature it kicks in, or whether it can be adjusted?