As seen in the pic, the water level was very low, causing the boiler to turn off. And there is some black junk in there.
Not sure why it keeps getting so low. This happened a couple times last winter and I had to manually feed water to keep it going. I also have the automatic feed turned up to 3 gallons per fill, with the maximum delay time. That seemed to fix the problem last winter. In the past, there was not all this black crud inside the glass.
This time I manually fed 10 gallons back into it, and the boiler is working.
There is no leaking water anywhere, not at the boiler or the radiators. And I don't see steam coming out of the chimney when the boiler is running.
Previously (last year) the system was venting a lot of steam from the hot water return lines, but that is not happening anymore since I replaced one of the relief valves that seemed to have had failed.
The boiler is a Weil-Mclain P-SGO-03 series 3 oil-fired steam boiler. The water feeder is Saf-Gard model VXT-120 and the low water cutoff is Saf-Gard 450.
Maybe there is a water leak inside the boiler? I don't know where else the water would be going. This doesn't happen all the time, just intermittently & especially in cold weather.
And I'm not sure if the water feeder just didn't activate this time, maybe it is not connected properly to the LWCO? The LWCO was showing the amber light, so it did know that the water level was low. And the water feeder seems to be working.
The oil company performed the annual tune-up on the boiler in July and everything seemed fine at that time. Should I just have them come back & clean it out again?