I have a winter setup with my heat pump and furnace, where I would like the furnace to run on low heat most of the time (it's a 2-stage furnace). I have an Ecobee 6, and I set the thresholds to the following:
Compressor Stage 2 Temperature Delta: 0.5C
Compressor to Aux Temperature Delta: 1C
Aux Stage 2 Temp Delta: 5.5C
Aux Stage 1 Max Runtime: Auto
I set the furnace back during the night by 5C, and it usually cools down somewhere between 3C and 5C at this time of year. I was hoping with my above thresholds, that the furnace would always turn on at stage 1, never stage 2. It does this on warmer nights, but not on the coldest.
From my testing, I have determined that the furnace will use stage 2 (high heat) when the temperature differential is somewhere between 4.3C and 4.8C. In other words, not even close to the 5.5C limit I set.
Does anyone know why this is? I can't set the limit any higher than 5.5C, since that's the max. (I presume internally the limit is 10F, but the furnace goes to stage 2 at around 8.5F difference.)
I know it's not a big deal, but I really don't like high heat unless I really need it (like when it's -30C outside.) I can work-around the issue by using different comfort profiles to slowly ramp up the temperature in the morning, but that has some downsides.