r/ukelectricians • • 15h ago

Can you help me understand how my bathroom has been wired?

Post image
8 Upvotes

Hi. I recently had a new bathroom put in. An electrician installed the ceiling light, 2 wall lights and an extractor fan with isolator switch.

He connected them all to a one-gang switch, located outside the bathroom.

He said I should easily be able to swap it for separate switches if I want. I'd like to be able to operate the fan one one switch, the ceiling light on another and the 2 wall lights one another. So I'd like to replace the one-gang switch with a 3-gang one.

But I don't understand the way it's wired in.

There are 4 cables: one 3-core-and-earth and 3 twin-and-earth.

TerminalConductors connected
COMBrown lives from T&E cables 1 and 2
L1Brown live and black switched-live from 3-core cable, plus brown live from T&E cable 3
Neutral connectorGrey from 3-core cable and blue from all 3 T&E cables
Earth connectorEarth conductors from all 4 cables

I tried connecting each of the cables to a one-gang switch separately, connecting the live to COM and the neutral to L1 but that didn't operate any of the lights or the fan, and connecting one of the T&E cables tripped the consumer unit.

If it was a simple swap, I'd do it myself but if it's more complicated, I'll get an electrician.

Before I give up, can anyone help me understand how the cabling works? Grateful for any advice.

Thanks.


r/ukelectricians • • 6h ago

Will this setup need to be upgraded to pass EICR?

Post image
1 Upvotes

Parents planning to turn part of their home into self catering and need EICR.


r/ukelectricians • • 6h ago

Is this OK???

Post image
0 Upvotes

Don't all get your panties in a twist. House has been rewired since this pic. but this is what I was greated by when I bought it.

Thought it would be appreciated here. And yes there is some cloth covered cable there!


r/ukelectricians • • 13h ago

Light switch fail after 15 years. Just replace or is something else wrong here?

Thumbnail gallery
0 Upvotes

r/ukelectricians • • 8h ago

LED bathroom bulb fortress of impenetrability

3 Upvotes

Hi, I live in a relatively new build flat (5 years old) and unfortunately two of the LED lights have always been dead since moving in a few years ago. Finally sound the motivation to do something about it!

1: The dead one in the living room is a "SPEAR 9w GU10 360 AC220-240V 50/60Hz 300k 8201m Ra90", it had a convex surface and some ridges that you could easily use to unscrew the bulb. So no issues there!

2: Unfortunately the dead one in the bathroom, seems to be different. It's not convex and has no ridges. I can't get the bulb or the white circle thing around it to budge at all and pushing the bulb in doesn't do anything either! A picture of it is below. Any ideas on how this is meant to be removed/replace? Thanks for any help!


r/ukelectricians • • 21h ago

Hi bay lights.

3 Upvotes

Are high bay lights in a commercial warehouse installed on a 13A single socket plug and socket arrangement fixed to the purlins subject to PAT?

It's more common for them to be wired via bus bar track or on klik plugs but I have seen them installed still on 13A sockets quite often.

A job we were on today with the lights plugged into 13A sockets someone said they should never be installed like that as now the lights will need to be PAT tested, it's the first time I've heard of that I have to admit.